Home / Services / Explosion proof electrical testing

Explosion proof electrical testing testing items

Explosion proof electrical safety testing is a comprehensive inspection and testing of explosive gas and vapor hazardous areas, as well as explosion-proof electrical boxes, explosion-proof motors, explosion-proof lamps and other explosion-proof equipment used in explosive and hazardous areas, and the environment in which they are used. In accordance with the requirements of national AQ3009-2007 "Electrical Safety and Explosion Prevention Specification for Hazardous Areas" and "Construction Acceptance Specification for Electrical Equipment Installation Engineering Explosion and Fire Hazardous Environment Electrical Equipment", it identifies and searches for explosion-proof safety hazards in the environment or equipment, and provides professional on-site explosion-proof safety solutions. Provide a legally binding testing report.


Explosion proof motor products

Product nameplate, explosion-proof certificate testing, electrical connection and installation structure testing, explosion-proof surface maintenance testing, fastener and protective measures testing, transparent component testing.

Explosion proof maintenance box and junction box products

Product nameplate, explosion-proof certificate testing, electrical connection and installation structure testing, explosion-proof structure testing, explosion-proof surface maintenance testing, fastener, protective measure testing, sealing component testing.

Explosion proof power distribution box, switch, lighting distribution box products

Product nameplate, explosion-proof certificate inspection, electrical connection and installation structure inspection, explosion-proof structure inspection, explosion-proof surface maintenance inspection, tight fitting parts, protective measures inspection, sealing part inspection.

Explosion proof instrument products

Product nameplate, explosion-proof certificate inspection, electrical connection and installation structure inspection, explosion-proof structure inspection, explosion-proof surface maintenance inspection, tight fitting parts, protective measures inspection, sealing part inspection.

Explosion proof lighting products

Explosion proof surface product nameplate, explosion-proof certificate testing, electrical connection and installation structure, maintenance testing, fastener, protective measure testing, transparent component testing.

Electrical circuit inspection in hazardous areas

General regulations:
1. Line laying method and wire diameter requirements;
2. Protection against potential mechanical damage, vibration, corrosion, and heat exposure;
3. Rated voltage requirements for cables and wires;
4. Selection of connection components such as junction boxes, distribution boxes, flexible joints, and isolation seals;
5. Requirements for the connection method of wires and cables.

Electrical circuit inspection in hazardous areas

Requirements for cable lines:
1、 Cable connection and branching requirements
2、 Isolation and sealing measures for cable lines passing through different hazardous areas
3、 Sealing requirements for the inlet of electrical equipment and junction boxes
4、 Requirements for flexible connections and flexible connecting pipes
5、 Seal the pipe openings outdoors and in areas prone to water ingress.

Electrical circuit inspection in hazardous areas

Steel pipe wiring:
1、 Selection of steel pipe materials
2、 Connections between steel pipes, electrical equipment, and steel pipe accessories
3、 Requirements for explosion-proof flexible joint connection
4、 Installation of isolation seals at designated locations
5、 Requirements for the production of isolation seals
6、 Installation of explosion-proof flexible connecting pipes at designated locations
7、 Requirements for explosion-proof flexible connecting pipes
8、 Sealing of excess holes on electrical equipment, junction boxes, and terminal boxes.

Grounding

Protective grounding:
1、 All non electrified exposed metals in explosive hazardous environments should be grounded or zeroed
2、 All electrical equipment in explosive hazardous environments must be specifically grounded
3、 The connection between the grounding main line (network) and the grounding body
4、 Protection and sealing requirements for grounding main lines crossing different environmental areas
5、 The dedicated grounding should be separately connected to the grounding main line (network), and the working neutral line should not be used as a protective grounding wire
6、 Requirements for the diameter of the dedicated grounding wire
7、 Grounding connection when installing cables into electrical equipment
8、 Install anti loosening bolts and other requirements.

Professional teamComplete qualificationsService guarantee

A testing report can be issued within one week, and if one test fails, another test will be conducted free of charge

Explosion proof electrical testing service process

The testing report issued is recognized by the state and society, and has specific legal effect.

On site investigation and data collection
Develop testing plan
Configure detection resources
On site inspection and recording
Data analysis and result judgment
Issue inspection report
liucheng01 (1).jpg
On site investigation and data collection
Develop testing plan
Configure detection resources
liucheng01 (2).jpg
On site inspection and recording
Data analysis and result judgment
Issue inspection report